Timing - Timers >

XM4H · ELAPSED TIME INDICATOR



TIMER RELAY MULTIESCALE, MULTIFUNCTION



XM4H analogue timer with elapsed-time % display: 8 modes, from 0.1 s to 50 h, 2 x SPDT 8A and control inputs. 48 × 48 panel.

Product type: Multifunction analogue timer
Installation: 48 × 48 mm panel, 11-pin socket
Modes: 8, by side DIP switch
Display: Percentage of elapsed time

Features

  • ✓Display showing the percentage of elapsed time and the timing status
  • ✓8 operating modes selected with the side DIP switch
  • ✓Time range from 0.1 s to 50 h: 4 ranges and 3 time bases on the front
  • ✓Start, count stop and reset inputs
  • ✓2 changeover outputs: the second timed or instantaneous, by DIP
  • ✓48 × 48 mm format with 11-pin socket
Supply
24…230 VAC · 12/24 VDC
Outputs
2 x SPDT 8A
Times
0.1 s … 50 h
Format
48 × 48 mm panel

How it works

  1. 1The mode and whether output 2 is timed or instantaneous are selected with the side DIP switch, with the unit powered off.
  2. 2The range and time base are chosen and the time is set on the front.
  3. 3Timing starts when the start contact (2 - 6) closes, or on power-up if it is already closed.
  4. 4Count stop (2 - 5) holds the time and reset (2 - 7) switches the output off. After a power cut, the cycle starts from zero.

Frequently asked questions

What does the display show?

The percentage of time elapsed and the timing status.

Which modes does it have?

Eight: ON on-delay · FL flicker · FO ON-flicker · OF1 ON/OFF-delay (1) · SF signal OFF-delay · OS one-shot · OF2 ON/OFF-delay (2) · OC ON-cycle.

What time range does it cover?

From 0.1 s to 50 h, with ranges of 0.1–1, 0.5–5, 1–10 and 5–50 in seconds, minutes or hours.


General information

Reference XM4H  (24 / 48 / 110 / 230 VAC · 12 / 24 VDC)
Series X · 48 × 48 mm panel
Product type Multifunction analogue timer

Electrical specifications

Supply 24 / 48 / 110 / 230 VAC · 12 / 24 VDC
Consumption 1.7 W
Outputs 2 x SPDT 8A 250 VAC: output 1 timed · output 2 timed or instantaneous

Times and functions

Modes ON on-delay · FL flicker · FO ON-flicker · OF1 ON/OFF-delay (1) · SF signal OFF-delay · OS one-shot · OF2 ON/OFF-delay (2) · OC ON-cycle
Ranges 0.1–1 · 0.5–5 · 1–10 · 5–50
Time bases Seconds, minutes or hours
Inputs Start, count stop and reset
Power cut The cycle always restarts from zero
Selection Side DIP switch, with the unit powered off

Indications

Display Percentage of elapsed time and status

Housing and mounting

Format 48 × 48 mm
Panel cut-out 45 × 45 mm
Fixing Snap-in bracket
Connection 11-pin socket
Material Grey polycarbonate UL94-V0
Weight ≈ 170 g

Environmental conditions

Operating temperature −10 to +55 °C
Storage temperature −25 to +85 °C

Standards and certifications

Compliance CE

Accessories

ZB11-0 · 11-pin socket for DIN rail  ·  PG11 · 11-pin socket with rear screw  ·  TBEU1E · 11-pin in-line socket  ·  MA7248 · frame from 72 × 72 to 48 × 48 mm  ·  MA9648 · frame from 96 × 96 to 48 × 48 mm  ·  MA96D48 · frame from 96 × 48 to 48 × 48 mm

Wiring: function of each terminal

Terminals Function
2 - 10 Supply
2 - 6 Start
2 - 5 Count stop
2 - 7 Reset
1 - 3 - 4 Timed changeover output 1
11 - 9 - 8 Auxiliary changeover output 2

The wiring diagram can be enlarged in the images below the photo.





Automatismos.com