Electrical control and measurements - Current relays >

ZCIx5xx · MAXIMUM INTENSITY CURRENT



INTENSITY CONTROL FOR MAXIMUM CURRENT



ZCIx5xx maximum current control relay with built-in toroid: 5, 10 and 20 A ranges, block or enable control input.

Product type: Maximum current control relay
Installation: DIN rail, 1 module
Measurement: Built-in toroid: one phase is passed through the hole
Application: Overload or jam: stops the motor before the thermal relay trips

Features

  • ✓Switches the output off when consumption exceeds the maximum: detects overloads and jams
  • ✓Built-in toroid: no external current transformer
  • ✓0 to 5, 0 to 10 and 0 to 20 A ranges depending on reference
  • ✓Front potentiometer setting
  • ✓Versions without control input (V), with block (B) or with enable (P)
  • ✓Detection and output status LEDs
  • ✓Only 17.5 mm of DIN rail
Supply
230 VAC or 24 VAC/VDC
Output
1 x SPDT 8A
Range
0–5 · 0–10 · 0–20 A
Format
1 DIN module · 17.5 mm

How it works

  1. 1One phase of the supply of the system to be monitored is passed through the hole on the side of the unit.
  2. 2With no current, the output is on, as is its LED.
  3. 3When the current reaches the value set with the potentiometer, its LED lights up and the output switches off.
  4. 4When the current drops back below the set value, the output switches on again.

Frequently asked questions

Does it need a current transformer?

No. The toroid is built in: just pass one phase through the hole on the side.

How is the reference read?

ZCI + control input (V none, B block, P enable) + function (5: maximum) + range (05, 10 or 20 A). For example, ZCIB510: with block, 0 to 10 A.

Which supply does it use?

230 VAC or 24 VAC/VDC. It must be stated in the order.


General information

Reference ZCIx5xx  (230 VAC or 24 VAC/VDC)
Replaces ZCIV02
No control input (V) ZCIV505 · ZCIV510 · ZCIV520
Block (B) ZCIB505 · ZCIB510 · ZCIB520
Enable (P) ZCIP505 · ZCIP510 · ZCIP520
Series Z · DIN rail
Function 5 · Maximum

Electrical specifications

Supply 230 VAC or 24 VAC/VDC (state in the order)
Consumption 1.7 W
Output 1 x SPDT 8A 250 VAC

Measurement and setting

Measurement Built-in toroid
Ranges 0 – 5 A · 0 – 10 A · 0 – 20 A
Setting Maximum setting with front potentiometer
Control input Block or enable, depending on model

Indications

LEDs Detection and output status

Housing and mounting

Format 1 DIN module · 17.5 × 90 × 58.5 mm
Fixing 35 mm rail (EN 60715)
Material Grey polyamide PA6 UL94-HB
Weight ≈ 72 g

Environmental conditions

Operating temperature −10 to +55 °C
Storage temperature −25 to +85 °C

Standards and certifications

Compliance CE · 2014/35/EU · 2014/30/EU

Wiring: function of each terminal

Terminals Function
1 - 3 Supply
2 - 3 Control input
4 - 5 - 6 Changeover output

The wiring diagram can be enlarged in the images below the photo.