Pump and motor relay >

MCT403 · MOTOR TEMPERATURE CONTROL



MOTOR TEMPERATURE CONTROL



MCT403 Pt100 absolute alarm for motors: pre-alarm, alarm and stop with reset. −25 to 250 °C, stop output 1 x SPDT 16A, digital display.

Product type: Absolute alarm thermostat for motors
Installation: DIN rail, plug-in connector
Function: Pre-alarm, alarm and motor stop by temperature
Sensor: 2- or 3-wire Pt100

Features

  • ✓Protects motors and windings: pre-alarm, alarm and stop
  • ✓Main motor stop output: 1 x SPDT 16A
  • ✓Programmable pre-warning output and active alarm indication output
  • ✓Alarm reset with the front push-button or a digital input
  • ✓Display with the actual temperature (red) and the alarm setpoint (green), in °C or °F
  • ✓Sensor break or short-circuit indication
  • ✓Lock of programming and setpoints
Supply
24 / 48 / 110 / 230 VAC
Outputs
SPDT 16 A + 2 SPST 8 A
Sensor
Pt100 · −25 … 250 °C
Reading
Digital display

How it works

  1. 1While the sensor temperature is below the setpoint, output 1 is on and the motor can run.
  2. 2If the temperature exceeds the pre-alarm value, output 2 (pre-warning) switches on.
  3. 3If it exceeds the alarm setpoint, output 1 switches off and stops the motor; output 3 signals the alarm.
  4. 4The alarm is reset with the ENTER button on the unit or by closing the RESET input.

Frequently asked questions

What is the difference between pre-alarm and alarm?

The pre-alarm (output 2) warns before the limit is reached; the alarm switches off output 1 and stops the motor.

How is it reset after an alarm?

With the ENTER button on the front or by closing the RESET input.

Which sensor does it use?

A 2- or 3-wire Pt100 sensor, with a range of −25 to 250 °C.


General information

Reference MCT403  (24 / 48 / 110 / 230 VAC)
Series M · modular DIN rail
Product type Absolute alarm thermostat with pre-warning

Electrical specifications

Supply 24 / 48 / 110 / 230 VAC
Output 1 (stop) 1 x SPDT 16A 250 VAC
Outputs 2 and 3 2 x SPST 8A (pre-alarm · alarm)

Sensor input

Sensor 2- or 3-wire Pt100
Range −25 to 250 °C (−13 to 482 °F)
Sensor error Open or short-circuited sensor indication

Functions

Pre-alarm Can be enabled, programmable value
Reset Front push-button or RESET input
Lock Programming and setpoints
Units °C or °F

Indications

Red display Actual temperature
Green display Alarm setpoint
Status LED Green: all correct · Red: alarm active

Housing and mounting

Format Modular 90.5 × 58.5 mm
Mounting DIN rail
Connection Plug-in connector