Pump and motor relay >

YRA006 · ALTERNATING RELAY FOR THREE MOTORS (PLUG-IN CONNECTORS)



ALTERNATING RELAY FOR THREE MOTORS (PLUG-IN CONNECTORS)



YRA006 alternating relay for 3 pumps: up to 3 outputs on at the same time, with 5 s between starts. DIN rail, plug-in connectors.

Product type: Pump alternating relay
Installation: DIN rail, plug-in connectors
Function: Alternation of groups of 3 pumps
Control: 3 external signal inputs

Features

  • ✓Each pulse on an input starts the next pump: all three share the running hours
  • ✓Up to 3 pumps running at the same time depending on the active inputs
  • ✓Outputs never start together: 5 s offset between starts
  • ✓Optocoupled inputs, 3.5 kV isolation
  • ✓Multi-voltage with transformer: 24, 48, 110, 230 or 380 VAC and 12 or 24 VDC
  • ✓Supply and output status LEDs
  • ✓Plug-in connectors: wired in the workshop and replaced on site
Supply
24 … 380 VAC · 12/24 VDC
Outputs
3 x SPST 10A
Pumps
3
Mounting
DIN rail

How it works

  1. 1Each time a pulse reaches an input, the YRA006 connects the pump that is next in the sequence.
  2. 2If one input is active and another one is activated, the corresponding output connects and both pumps run together.
  3. 3If two or more inputs are activated at the same time, the outputs start 5 s apart, beginning with the one that is next.
  4. 4This avoids starting peaks and equalises the hours of the three pumps.

Frequently asked questions

Can all three pumps start at the same time?

All three can run together, but they never start together: there are 5 s between starts.

Which signal does it need?

External contacts (level relays, pressure switches or float switches) on inputs I1, I2 and I3.

Why the 5-second offset?

So that the motors do not start together and there are no current peaks or shocks in the installation.


General information

Reference YRA006  (24 / 48 / 110 / 230 / 380 VAC · 12 / 24 VDC)
Series Y · modular DIN rail
Product type Pump alternating relay with external signal
Pumps 3

Electrical specifications

Supply 24 / 48 / 110 / 230 / 380 VAC · 12 / 24 VDC
Supply type Transformer (VAC)
Consumption 2.8 VA
Outputs 3 x SPST 10A
Offset between starts 5 s

Inputs

Inputs I1, I2 and I3
Type 15 VAC optocoupled · 3.5 kV isolation

Indications

LEDs Supply and output status

Housing and mounting

Format 90 × 62.5 × 35 mm
Mounting DIN rail
Connection Plug-in connectors
Material Grey polycarbonate UL94-V0
Weight ≈ 170 g

Environmental conditions

Operating temperature −10 to +55 °C
Storage temperature −25 to +85 °C

Standards and certifications

Compliance CE · 2014/35/EU · 2014/30/EU

Wiring: function of each terminal

Terminal Function
1 Supply (with 12)
2 Input I1 (with 11)
3 Input I2 (with 11)
4 Input I3 (with 11)
7 Output O1 (with 10)
8 Output O2 (with 10)
9 Output O3 (with 10)
10 Output common
11 Input common
12 Supply (with 1)

The wiring diagram can be enlarged in the images below the photo.