Temperature - Temperature converters >

VCT010 · TEMPERATURE CONVERTER FOR NTC PROBE



TEMPERATURE CONVERTER FOR NTC PROBE



VCT010 temperature converter for NTC 10 kΩ sensor: 0 – 10 V output from −15 to 85 °C, sensor error LED, 22.5 mm DIN housing.

Product type: Temperature converter
Installation: DIN rail, 22.5 mm housing
Input: NTC 10 kΩ sensor (B25/85 = 3977 K)
Output: Analogue 0 – 10 V

Features

  • ✓Converts the temperature of an NTC sensor into a 0 – 10 V signal for PLCs, drives and recorders
  • ✓Range from −15 to 85 °C: 0 V at −15 °C or below and 10 V at 85 °C or above
  • ✓Error LED if the sensor breaks or short-circuits
  • ✓Power LED
  • ✓22.5 mm housing for DIN rail
Supply
100 – 240 VAC
Output
0 – 10 V
Sensor
NTC 10 kΩ
Format
22.5 mm · DIN rail

How it works

  1. 1The NTC sensor is connected to the input (terminals 6 - 8) and the PLC analogue input to the output (terminals 3 - 4).
  2. 2The converter gives a voltage from 0 to 10 V depending on the temperature read.
  3. 3At −15 °C or below the output is 0 V; at 85 °C or above, 10 V.
  4. 4If the sensor breaks or short-circuits, the error LED on the front lights up.

Frequently asked questions

Which sensor does it need?

An NTC 10 kΩ sensor with B25/85 = 3977 K.

Which output does it give?

A voltage from 0 to 10 V: 0 V at −15 °C or below and 10 V at 85 °C or above.

How does it signal a sensor fault?

If the sensor breaks or short-circuits, the error LED on the front lights up.


General information

Reference VCT010  (100 – 240 VAC)
Series V · 22.5 mm DIN rail module
Product type Temperature converter

Electrical specifications

Supply 100 – 240 VAC
Consumption 1.7 W
Output 0 – 10 V

Sensor and measurement

Sensor NTC 10 kΩ (B25/85 = 3977 K)
Range −15 … 85 °C
Sensor failure Error LED for break or short circuit

Indications

LEDs Power and sensor error

Housing and mounting

Format 22.5 × 90 × 58.5 mm
Fixing DIN rail
Material Grey polyamide PA6 UL94-HB
Weight ≈ 80 g

Environmental conditions

Operating temperature −10 to +55 °C
Storage temperature −25 to +85 °C

Standards and certifications

Compliance CE · 2014/35/EU · 2014/30/EU

Wiring: function of each terminal

Terminals Function
1 - 2 Supply
3 - 4 0 - 10 V output
6 - 8 NTC sensor input

The wiring diagram can be enlarged in the images below the photo.