Timing - Timers >

ZETV02 · STAR-DELTA TIMER



TIME RELAY STAR DELTA



ZETV02 star-delta timer: motor starting with a safety pause adjustable from 20 ms to 2 s. 230 VAC or 24 VAC/DC, 17.5 mm housing.

Product type: Star-delta starting timer
Installation: DIN rail, 1 module
Function: Star-delta starting with safety pause

Features

  • ✓Large motors start in star and switch to delta: no current peaks
  • ✓Pause adjustable from 20 ms to 2 s between star and delta: prevents short circuits between contactors
  • ✓Star time adjustable from 5 to 50 s
  • ✓Two supply voltages: 230 VAC and 24 VAC/DC
  • ✓Operation LED
  • ✓1-module housing (17.5 mm)
Supply
230 VAC · 24 VAC/DC
Output
1 x SP3T 8A
Star time
5 … 50 s
Mounting
DIN rail · 17.5 mm

How it works

  1. 1When the start command is given, the star output closes and the motor starts with reduced current.
  2. 2After the set star time (5 to 50 s), the star output opens.
  3. 3After the safety pause (20 ms to 2 s), the delta output closes.
  4. 4The pause prevents both contactors from being closed at the same time.

Frequently asked questions

What is the pause between star and delta for?

So that the star contactor is fully open before the delta contactor closes and there is no short circuit between them. It is adjustable from 20 ms to 2 s.

Which star time does it allow?

From 5 to 50 seconds.

What is the difference with the VETV02?

The ZETV02 is 17.5 mm wide and is supplied at 230 VAC or 24 VAC/DC; the VETV02 is multi-voltage with transformer, up to 380 VAC.


General information

Reference ZETV02  (230 VAC · 24 VAC/DC)
Series Z · modular DIN rail 17.5 mm
Product type Star-delta starting timer

Electrical specifications

Supply 230 VAC · 24 VAC/DC
Output 1 x SP3T 8A
Contact 1 common with 2 normally open contacts

Times

Star time Adjustable from 5 to 50 s
Star-delta pause Adjustable from 20 ms to 2 s

Indications

LED Operation

Housing and mounting

Format Modular 1 module · 17.5 × 90 × 58.5 mm
Mounting 35 mm DIN rail (EN 60715)

Wiring: function of each terminal

Terminals Function
1 - 3 230 VAC supply
1 - 2 - 3 24 VAC/DC supply
5 - 6 Star output
4 - 6 Delta output

The wiring diagram can be enlarged in the images below the photo.